I. Main Circuit Schemes
The main circuit schemes of the XBGCS cabinet total 32 groups and 118 specifications, not including schemes and specifications derived from changes in the control and protection of auxiliary circuits. They include the needs of power generation, power supply, and other power users, with a rated operating current of up to 5000A, suitable for selection with distribution transformers of 2500kVA and below. In addition, to meet the needs of power supply systems with high power factor requirements, capacitor compensation cabinets are designed, and reactor cabinets can be selected based on comprehensive investment needs.
II. Auxiliary Circuit Schemes
The XBGCS auxiliary circuit diagram collection contains a total of 120 auxiliary circuit schemes, divided into two volumes. The first volume, "AC Operation Part", has 63 schemes in total, and the second volume, "DC Operation Part", has 57 schemes in total. The auxiliary circuit schemes of the DC operation part are mainly used for the low-voltage auxiliary (station) power systems of power plants and substations. They are suitable for the low-voltage auxiliary power systems of units of 200MW and below and 300MW and above, and are general control methods for working (standby) power incoming lines, power feeder lines, and motor feeder lines.
The auxiliary schemes of the AC operation part are mainly used for the low-voltage power distribution of substations in industrial and mining enterprises and high-rise buildings. There are 6 combination schemes suitable for dual-power-supply operation control, with operating electrical interlocking and automatic/self-recovery control circuits, which can be directly adopted in engineering design.
The DC-controlled control power supply is DC 220V or 110V, and the AC control power supply is AC 380V or 220V, composed of draw-out unit assembly cabinets. The 220V control power supply is a common control power supply supplied by a dedicated control transformer in the cabinet itself. The common control power transformer uses an ungrounded control transformer, and a 24V power supply is reserved for use when weak-current signal lamps are needed.
For the installation location of the electricity meters, the method of introducing voltage signals, and their installation and use requirements, please refer to the "Compilation Notes" of the auxiliary circuit diagrams.
III. Main Busbars
1. To improve the thermal stability of the busbars and improve the temperature rise of the contact surfaces, all equipment uses TMY-T2 series hard copper busbars, with the copper busbars fully tin-plated, and fully silver-plated copper busbars can also be selected.
2. The horizontal busbars and vertical busbars are installed separately in isolated compartments inside the cabinet.
3. The neutral grounding busbar uses a hard copper busbar. It is a continuous horizontal protective earth neutral (PEN) or grounding + neutral (PE+N).
IV. Selection of Electrical Components
1. GCS cabinets mainly use electrical components with high technical standards and stable performance indicators, and electrical components that have been mass-produced domestically with imported technology.
2. Main switch
For incoming and feeder switches of 630A and above, the DW45 series is mainly selected; the DW48 series, AE series, 3WE or ME series can also be selected; if considered necessary, imported M series or F series can also be selected.
3. For feeder and motor control switches below 630A, molded case series such as the TG series, CM1 series, NM series, CDM series, and TG30 series are mainly selected.
4. To improve the dynamic stability of the main circuit, a combined busbar clamp and insulating support dedicated to the GCS series have been designed, molded from high-strength, flame-retardant synthetic thermoplastic materials, with high insulation strength, good self-extinguishing performance, and a unique structure.
5. To reduce the temperature rise of the partition plates, plug-in connectors, and cable lugs between functional units, a dedicated adapter for GCS cabinets has been designed, with large adapter capacity and reduced temperature rise.
6. When the design department selects new electrical components with better performance and more advanced technology according to user needs, because the GCS series cabinets have good versatility, it will not cause difficulties in manufacturing and installation due to frequent updates of electrical components.