Our indoor high-voltage vacuum circuit breaker series is primarily used in the indoor power distribution systems of industrial/mining enterprises, power plants, and substations, serving as the core protection and control device for switching load and fault currents. The range covers fixed, handcart, side-mounted, and three-position vacuum circuit breakers, with voltage ratings from 12kV to 40.5kV.
Featuring an integrated sealed pole column design, the breakers achieve compactness, high reliability, and maintenance-free operation, with a mechanical life of up to 20,000 operations — suitable for frequent-switching applications. They are compatible with switchgear such as KYN28 and XGN series, and customized production and technical selection advice are available based on cabinet dimensions, operating voltage, and control mode.
Wenzhou Xubian Electric Co., Ltd. is a technology-driven China Indoor Vacuum Circuit Breaker Manufacturer and Custom Indoor Vacuum Circuit Breaker Supplier, specializing in the production, sales and after-sales maintenance of high- and low-voltage complete switchgear systems.
We have a dynamic and innovative team for R&D, design, management and marketing, backed by solid R&D and production competence.
Following our quality policy: “Survival through Quality, Development through Innovation, Continuous Improvement, Customer Satisfaction”, we enforce strict control over all production stages to ensure 100% qualified finished goods. Our workshop is well‑equipped with full‑range processing facilities, testing apparatus and advanced inspection solutions.
Wenzhou Xubian Electric Co., Ltd. manufactures and supplies the Indoor Vacuum Circuit Breaker Manufacturer range: three-phase indoor vacuum breakers from 12 kV to 40.5 kV that switch load and fault current inside industrial, mining, power-plant and substation distribution systems. Fixed, handcart, side-mounted and three-position constructions are all built on integrated sealed pole columns with the spring operating mechanism mounted on the breaker body.
We build these breakers as standalone units for switchgear manufacturers and as part of our own high- and low-voltage complete equipment. Each configuration is selected against the cabinet it will operate in — mounting style, phase spacing, rated current, short-circuit level and control voltage are confirmed before production, and OEM or ODM variants are built to customer drawings, branding and destination standard.
The series covers the switching duties found in a typical indoor substation: incoming and outgoing feeders, busbar sectioning, motor and transformer protection, and metering functions. Models differ in mounting method, pole arrangement and current path, so the same electrical duty can be delivered in a cabinet footprint that suits the switchgear design.
| Model family | Construction | Voltage | Where it fits |
|---|---|---|---|
| ZN63(VS1)-12 fixed / handcart | Integrated mechanism; fixed unit or handcart with propulsion mechanism; solid-sealed poles | 12 kV | KYN28A-12 (GZS) centre-mounted switchgear and XGN fixed cabinets, including frequent-operation duty |
| ZN63(HR1)-12 handcart | Withdrawable handcart with dedicated propulsion mechanism | 12 kV | KYN28A-12 (GZS1) centre-mounted cabinets; contact engagement 15–25 mm on assembly |
| ZN63(VS1)-12 side-mounted | Fixed, side-mounted pole arrangement | 12 kV | Fixed-type cabinets, ring main units, box-type substations and non-standard supply systems |
| VSC-12 miniaturized side-mounted | Compact side-mounted body | 12 kV | Space-restricted fixed cabinets and retrofit applications |
| VZG-12GD three-position | Three-position vacuum interrupter unit | 12 kV | Compact switchgear requiring combined switching, isolation and earthing positions |
| VZF-12R sealed combination | Sealed vacuum load switch with fuse combination | 12 kV | Circuits needing load switching plus fuse-based short-circuit protection in one sealed unit |
| VS1-24 | Indoor vacuum breaker with integrated mechanism | 24 kV | 24 kV indoor distribution panels and industrial feeders |
| ZN85-40.5 | 40.5 kV indoor vacuum breaker | 40.5 kV | 40.5 kV metal-enclosed switchgear in plants and substations |
| PT handcart functional unit | Withdrawable functional handcart | 12 kV | Voltage-transformer and auxiliary compartments of withdrawable cabinets |
Mounting style drives the cabinet interface, the interlocking scheme and the maintenance routine, so we confirm it at the quotation stage rather than at delivery.
Bolted into XGN and similar fixed cabinets. Fewer moving parts, straightforward cable termination, suited to circuits that are isolated at the upstream device for service.
Fitted with a dedicated propulsion mechanism for KYN28A-12 centre-mounted cabinets, allowing the breaker to be racked between service and test positions.
Used where depth is limited or where switching, isolation and earthing must be combined inside a compact enclosure.
All variants use integrated sealed pole columns, which keeps the interrupters compact, protects the vacuum chamber from contamination and removes routine contact maintenance from the operating cycle.
The figures below describe the 12 kV ZN63 family and are representative of the design basis we quote against. Values for 24 kV and 40.5 kV models are confirmed per configuration.
| Parameter | Value |
|---|---|
| Rated voltage / maximum operating voltage | 12 kV / 12 kV |
| Rated current | 630 A to 4000 A |
| Rated short-circuit breaking current | 20/25 kA, 31.5 kA, 40 kA |
| Rated short-circuit making current (peak) / peak withstand | 50/63 kA, 80 kA, 100 kA |
| 4 s short-circuit withstand current | 20/25 kA, 31.5 kA, 40 kA |
| Power-frequency withstand, 1 min | 42 kV to earth, 48 kV across open contacts |
| Lightning impulse withstand (peak) | 75 kV to earth, 85 kV across open contacts |
| Rated operating sequence | O-0.3 s-CO-180 s-CO |
| Mechanical life / short-circuit breaking operations | 20,000 operations / 50 |
| Contact gap / overtravel | 11 ± 1 mm / 3.5 ± 0.5 mm |
| Opening and closing asynchronism | ≤ 2 ms |
| Average opening / closing speed | 0.9–1.2 m/s / 0.5–0.8 m/s |
| Opening time / closing time | ≤ 0.05 s at maximum operating voltage (≤ 0.08 s at minimum) / 0.1 s |
| Main circuit resistance per phase | ≤ 50 μΩ at 630 A, ≤ 45 μΩ at 1250 A |
| Contact wear allowance | 3 mm cumulative |
| Operating mechanism rated voltage | AC or DC 110 V, 220 V |
These breakers are the protection and control device for indoor power distribution in industrial and mining enterprises, power plants and substations. Vacuum interruption makes them particularly suitable for circuits that switch rated current often or clear short-circuit current repeatedly, because the arc is extinguished in a sealed chamber rather than in open air.
The installation environment is defined at selection: ambient temperature from −10 °C to +40 °C, storage and transport down to −30 °C, altitude up to 1000 m, daily average relative humidity up to 95% and seismic intensity up to Grade 8. Where a project exceeds these conditions, insulation levels are increased accordingly and the rating is agreed in writing.
The spring operating mechanism is integrated with the breaker body, which simplifies the cabinet linkage and keeps the trip and close characteristics consistent across a batch. Closing and opening coils are supplied for AC or DC 110 V and 220 V control supplies, matching the DC systems common in substations and the AC supplies used in industrial plants.
For switchgear projects we align the breaker with the cabinet's protection and control scheme — manual operation, electrical operation from a local control point, or remote control through the panel's intelligent protection and monitoring devices. Auxiliary and status contacts are agreed with the wiring diagram so that position, spring state and trip signals reach the protection relay or RTU without field modification.
Incoming materials and purchased components are inspected on arrival and non-conforming supplies are rejected before they enter the line. During production, QC staff carry out in-process patrol checks through pole assembly, wiring and cabinet processing so that defects are caught before the breaker is closed up.
Semi-finished units pass insulation resistance, power-frequency withstand and DC resistance measurements before moving to the next stage. Finished breakers undergo complete factory tests including voltage withstand, temperature-rise and functional verification, and test reports accompany the shipment. Our complete switchgear programme is built around the GB 3906 and IEC 62271 framework, and custom products are supplied to CE, ISO 9001 and CCC requirements where the destination market calls for them.
Breakers ship as tested units with export packing, manuals and test documentation. When a handcart breaker is fitted into its cabinet, the engagement dimension between moving and fixed contacts must be set to 15–25 mm; we confirm this dimension against the cabinet drawing before dispatch.
Send these project inputs and we return a technical selection, a drawing and a quotation:
As a China indoor vacuum circuit breaker manufacturer, we support OEM and ODM projects from drawing design through prototype confirmation to mass production. Standard models are normally ready in 7–15 working days; non-standard breakers follow the agreed drawing and production schedule.
Our breakers are also delivered as part of the wider High-Voltage Complete Switchgear range, where breaker, isolating contacts, earthing switch and protection devices are assembled, wired and tested as one unit before shipment. That single-source scope shortens site work for projects that need both the breaker and the cabinet.
The ZN63(VS1)-12 and ZN63(HR1)-12 families are built for KYN28A-12 (GZS, GZS1) centre-mounted cabinets and XGN fixed cabinets. Side-mounted and miniaturized versions suit fixed-type switchgear, ring main units and box-type substations.
The series covers 12 kV, 24 kV and 40.5 kV. At 12 kV, rated current runs from 630 A to 4000 A with short-circuit breaking capacities of 20/25 kA, 31.5 kA and 40 kA, matched to the short-circuit level of the installation.
Yes. The mechanism is integrated with the breaker body, so the same electrical design is supplied as a fixed-mounted unit or fitted with a dedicated propulsion mechanism to form a handcart unit for withdrawable cabinets.
The 12 kV models are rated for 20,000 mechanical operations and 50 rated short-circuit current breaking operations, with an operating sequence of O-0.3 s-CO-180 s-CO. This supports circuits that switch rated current frequently.
OEM and ODM supply is available, covering technical drawings, prototype testing, nameplate and branding, packing and export documents. Non-standard configurations are confirmed against the cabinet drawing before the technical agreement is signed.
Each order ships with factory test reports, operating manuals and export documentation, with installation guidance and online technical support available after delivery.