12kV Medium Voltage Switchgear Custom

Home / Products / 12kV Medium Voltage Complete Switchgear Equipment
Wenzhou Xubian Electric Co., Ltd.
About Us

XUBIAN ELECTRIC POWER YOU CAN TRUST

Wenzhou Xubian Electric Co., Ltd.
  • 10+

    Years Experience

Wenzhou Xubian Electric Co., Ltd. is a technology-driven China 12kV Medium Voltage Switchgear Manufacturer and Custom Compact Switchgear Supplier, specializing in the production, sales and after-sales maintenance of high- and low-voltage complete switchgear systems.

We have a dynamic and innovative team for R&D, design, management and marketing, backed by solid R&D and production competence.

Following our quality policy: “Survival through Quality, Development through Innovation, Continuous Improvement, Customer Satisfaction”, we enforce strict control over all production stages to ensure 100% qualified finished goods. Our workshop is well‑equipped with full‑range processing facilities, testing apparatus and advanced inspection solutions.

View More
Wenzhou Xubian Electric Co., Ltd.

Company Philosophy

Quality Centered, Quality First, Win-Win Cooperation

Company Mission

To become a trusted global manufacturing partner for power transmission and distribution equipment.
  • Factory equipment
  • Factory equipment
  • Factory equipment
  • Factory equipment
  • Factory equipment
  • Factory equipment
  • Factory equipment
  • Factory equipment
  • Warehouse
  • Warehouse
News Center

Keep Up To Date With Our Latest News.

View More

Certificate Of Honor

  • 1
  • 2
12kV Medium Voltage Complete Switchgear Equipment Industry knowledge

Wenzhou Xubian Electric Co., Ltd. manufactures complete 12kV medium voltage switchgear for urban distribution networks, industrial and mining installations, and renewable energy grid-connection points. Our range brings sealed SF6 ring main units, solid-insulated switchgear, air-insulated ring network cabinets and box-type fixed or withdrawable metal-enclosed switchgear under one engineering platform, supplied as assembled, wired and factory-tested units.

Production runs from Liushi Town, Yueqing, Zhejiang, with in-house sheet-metal processing, assembly and factory inspection, and OEM/ODM builds follow the customer voltage class, control mode and branding. As a 12kV Medium Voltage Complete Switchgear Equipment manufacturer, we coordinate the single-line layout, insulation coordination and the interface between the MV cabinet, the Box-Type Substation and the downstream distribution boards.

Our 12kV Medium Voltage Range

As a 12kV Medium Voltage Switchgear Manufacturer, we match product configuration to the application, operating limits, interfaces and acceptance criteria defined for each project.

Every family below is built around the same 12kV insulation platform, with 24kV and 36–40.5kV variants available in the same cabinet architecture. Selection is driven by the fault level, the switching duty of each feeder and the space available at the ring network point.

Sealed and gas-insulated ring main units
XBSRM-12 fully insulated, fully sealed metal-enclosed switchgear; XBRM6(XGN)-24 compact ring network equipment; RM-40.5 inflatable cabinet for 36–40.5kV secondary distribution. Gas tanks are welded from 3 mm stainless steel and sealed for life.
Solid-insulated and environmental cabinets
XBGN-12 solid insulated switch equipment and XBHBN-12 full insulation ring network cabinet, for projects that specify a gas-free insulating path and low partial-discharge levels in damp or polluted rooms.
Air-insulated metal-enclosed switchgear
HXGN-12, HXGN2-12, HXGN17-12 and HXGN66-12 cabinets, plus XB45G-12(Z) box-type fixed and XB55K-12(Z) removable air-insulated units, for indoor substations where front access and conventional maintenance routines are preferred.

Range and Application Fit at a Glance

Equipment family Insulation and enclosure Typical fit Configuration notes
XBSRM-12 metal-enclosed switchgear SF6, IP67 welded gas tank, sealed for life Ring network points, cable branch boxes, compact distribution rooms C, F, V, D, SL, M and PT units; front, right, top or rear cable entry
XBRM6(XGN)-24 compact ring network equipment SF6 fully sealed, IP67 gas tank / IP4X enclosure Industrial parks, airports, tunnels, wind power stations 630 A, 20 kA/4 s, multi-loop ring main layouts
RM-40.5 inflatable cabinet SF6 gas compartment, modular stainless steel tank 36–40.5kV secondary distribution, compact substations, mining, wind plants Ten standard combinations, C/D/De/F/V functional units
XBGN-12 solid insulated switch equipment Solid dielectric, metal enclosure Harsh, humid or polluted indoor rooms Gas-free insulation path, small footprint
XBHBN-12 full insulation ring network cabinet Full insulation, environmental design Urban distribution rooms with tight clearances Ring, transformer and riser units in one lineup
HXGN-12 / HXGN2-12 / HXGN17-12 Air insulated, metal enclosed Indoor substations, plants, commercial buildings Fixed or enclosed box-type structures, conventional access
HXGN66-12 fixed metal enclosed Air insulated, fixed structure Feeder and incoming panels with simple duty cycles Vacuum breaker or load switch fitted per feeder
XB45G-12(Z) box-type fixed closed Air insulated, closed box frame Secondary distribution and small industrial substations Compact plate layout, cable bottom entry
XB55K-12(Z) removable air insulated Air insulated, withdrawable truck Plant networks needing fast breaker changeover Withdrawable vacuum breaker, interlocked compartments

Insulation Architecture and Where Each Type Fits

Sealed gas units

The XBSRM-12 and XBRM6(XGN)-24 place every live part and the switching device inside a welded stainless steel gas tank rated IP67, so humidity, salt fog, flooding and dust do not reach the insulation. Cable connections use moulded silicone connectors, which keeps the cabinet maintenance-free and suited to street-side and outdoor ring network points.

Solid insulation

XBGN-12 and XBHBN-12 route the insulation through solid dielectric material rather than gas, which suits buildings with restricted gas handling procedures and rooms with sustained damp. These cabinets keep the compact footprint of a ring main unit while allowing conventional visual inspection of the enclosure.

Air-insulated metal enclosures

HXGN and XB45G/XB55K cabinets use air clearance and metal partitions with interlocked compartments, giving maintenance teams direct access to breaker trucks, CTs and cable terminations. They are the practical choice where a substation room has space and where project standards call for withdrawable breakers.

Ratings, Capacity and Repeatability

The 12kV platform is engineered around defined ratings so that protection settings, cable sizes and earthing calculations can be fixed before production.

  • Rated voltage 12kV; 24kV and 36–40.5kV variants in the same cabinet families
  • Rated current 630A on load-switch and busbar circuits; 630A or 1250A on vacuum breaker modules
  • Power-frequency withstand 42kV phase-to-phase, 48kV across the open gap; lightning impulse 75kV / 85kV
  • Short-time withstand 20kA for 3s; short-circuit breaking up to 31.5kA; peak making up to 80kA
  • SF6 gas at 1.4 bar absolute at 20°C, leakage rate 0.2% per year, 3.0mm stainless steel tank
  • Mechanical life up to 5,000 operations on load-switch units and 2,000 on breaker units
  • Busbar 400mm² copper, earthing busbar 150mm² copper; loop resistance held to the module limits

Designs reference GB/T11022, GB3906, GB1984, GB3804, GB1985 and GB16926 together with IEC60056, IEC60129, IEC60265, IEC60298, IEC60420 and IEC60694, so a project specification written to either framework can be matched.

Application Fit Across Distribution and Renewable Projects

The same cabinet architecture serves urban distribution, industrial plants and generation sites, with the insulation type and unit mix adjusted to the duty.

  • Urban and residential distribution: sealed ring main units at pavement ring points, with metering and PT units in the same lineup
  • Industrial and mining networks: air-insulated withdrawable or fixed cabinets where breaker replacement time matters
  • Solar farms: MV collection cabinets and incoming units matched to inverter transformer ratings and cable entry direction
  • Wind farms: compact sealed ring main units for tower-base and collector substations exposed to humidity and salt fog
  • Package and box-type substations: MV cabinets sized to the enclosure footprint and coordinated with the transformer and LV board

Because we also build Low Voltage Complete Electrical Equipment and transformers, the MV switchgear, transformer and LV distribution board are dimensioned as one package rather than three separate purchases.

Control, Protection and Automation Integration

Each cabinet is wired for the operating mode agreed at the drawing stage, whether that is manual operation, local electric operation or remote control from a distribution automation system.

  • Vacuum circuit breakers with FK-12 CF-type or V-type spring operating mechanisms
  • Load switches, earthing switches and solid-insulated breakers from our Inflatable Cabinet Accessories Series fitted to the unit schedule
  • Current and voltage transformers, protection relays, multifunction meters and fault indicators mounted in the LV compartment
  • Auxiliary contacts, remote signalling terminals and trip/close circuits prepared for SCADA or RTU connection
  • Mechanical interlocking and position indicators meeting five-proof requirements, with mimic diagrams on the front panel

Configuration and OEM/ODM Support

We build to a confirmed unit schedule rather than a catalogue number. The unit codes set the function of each compartment, and the enclosure is then dimensioned around the cable boxes and busbar route.

  • C load switch, F load switch-fuse combination, V vacuum breaker, D direct cable, SL bus coupler, M metering and PT units
  • Front, right, top or rear cable entry; front-to-back or left-to-right cabinet arrangements on insulated busbars
  • Panel colours RAL7012 for front plates and RAL7035 for side panels and cable compartment covers
  • OEM and ODM work covering drawing design, prototype confirmation, private-label plates and export packing
  • Altitude and ambient adaptation discussed against the standard 40°C maximum, -40°C minimum and 2000m altitude envelope

Quality Control, Factory Testing and Acceptance

Incoming materials and purchased components are inspected on arrival and rejected at source when they do not conform. QC staff then patrol winding, assembly, wiring and cabinet processing, and semi-finished units must pass insulation resistance, voltage withstand and DC resistance checks before moving on.

  1. Finished-product factory tests: power-frequency voltage withstand, temperature rise and function verification
  2. Interlock and operation sequence checks on every breaker, load switch and earthing switch
  3. Test report issued with the equipment; shipment released only after full qualification
  4. Factory test reports supplied for project files, with assistance on further certification where a target market requires it

Installation, Maintenance and Spare Parts

Sealed units are installed on a galvanised sheet-metal frame, and the gas tank carries a pressure relief device that vents to the front or rear if internal pressure rises. Because the tank is a pressure-sealed system, normal service work is limited to external inspection, cable termination checks and operating mechanism maintenance.

  • Documentation with each shipment: drawings, manuals, factory test reports and export documents
  • Installation guidance and online technical support during commissioning
  • Warranty support for repair, replacement and return, with spare parts available after the warranty period
  • Replacement breakers, spring mechanisms, earthing switches and load switches available for the cabinet families we supply

Information We Use to Configure Your Solution

A workable proposal needs the electrical duty and the physical constraints of the room, not just a voltage figure. The items below are what our engineering team works from when preparing drawings and a quotation.

  • System voltage, frequency and earthing arrangement, plus the prospective short-circuit current
  • Single-line diagram with feeder functions, rated current per unit and transformer capacity
  • Cable type, size and quantity per entry, and the preferred entry direction
  • Indoor or outdoor installation, ambient temperature range, humidity, pollution and salt-fog exposure
  • Protection, metering and control scheme, including relay type and remote signalling protocol
  • Room layout, available footprint, front access clearance and busbar arrangement
  • Target standards, panel colour, labelling language, branding and packing requirements

Frequently Asked Questions

Which 12kV switchgear suits a compact indoor distribution room?

XBSRM-12 sealed ring main units and XBHBN-12 full insulation cabinets give the smallest footprint because the insulation distance is inside the gas tank or solid dielectric. Where a walk-in room is available and withdrawable breakers are preferred, HXGN-12 or XB55K-12(Z) cabinets provide front access with a larger footprint.

Can you supply MV switchgear for solar and wind projects?

Yes. Solar collection circuits are normally built with MV incoming and feeder cabinets matched to the inverter transformer ratings, while wind collector points are usually sealed ring main units chosen for humidity and salt-fog resistance. Both are configured from the same 12kV platform with project-specific protection and metering.

Do you provide OEM and ODM builds under our brand?

We do. The process runs from requirement assessment and technical proposal through drawing and specification confirmation, prototype testing where the design is non-standard, mass production, private-label branding and export packing. Drawings, specifications and test documents are issued for approval before production starts.

What tests are performed before the switchgear is shipped?

Finished cabinets go through power-frequency voltage withstand, temperature rise and functional verification, following insulation resistance and DC resistance checks at the semi-finished stage. Interlock and operation sequences are also verified, and the factory test report travels with the equipment.

How are shipment and installation supported?